Configuration Number |
Location Number |
Name |
Default Value |
Description |
C000 |
L010 |
Off-Peak Method of Charge Control |
5 |
Sets the method of brick core charging to be used during off-peak (charge) periods. Heater is configured for automatic charge control, which is a value of five (5). To utilize manual charge control, change the value to six (6) |
C001 |
L012 |
Start Brick Core Charge Set Point |
60 |
If utilizing automatic charge control as set in C000, this value indicates the outdoor temperature at which the heater will start charging. |
C002 |
L013 |
Full Brick Core Charge Set Point |
20 |
If utilizing automatic charge control as set in C000, this value indicates the outdoor temperature at which the heater will target a full core charge. |
C003 |
L020 |
Power Line Carrier (PLC) Channel Selection |
3 |
If using PLC communication, this setting must match the channel setting in the Steffes PLC transmitting device. A value of zero indicates power line carrier communication is disabled. |
C004 |
L035 |
Optional Controls Configuration |
154 |
Notifies the unit when Time Clock Module or Outdoor Sensor are being utilized.
Value |
Configuration Description |
154
|
No Time Clock Module/Utilizing PLC or Manual Charge Control
|
155
|
No Time Clock Module/Outdoor Sensor Wired to the Heater
|
158
|
Time Clock Module/Manual Charge Control
|
159
|
Time Clock Module/Outdoor Sensor Wired to the Heater
|
|
C005 |
L036 |
Control Switch Configuration |
0 |
If utilizing power line carrier control, the time clock module, line voltage control, or Low Voltage Peak control switches that close for Peak times, this value should be zero. For all other applications, this value should be one (1).
|
C006 |
L037 |
Output Control Configuration |
6 |
This configuration MUST be set to a value of six (6) for all 2100 Series room heating units. |
C007 |
L043 |
Charge Factor |
30 |
This configuration should be set to a value of thirty (30) in most cases. Higher numbers indicate more aggressive charging for Algorithms 4, 5, 6, and others that use Sensorless Charging. See C000 above. |
C010 |
L048 |
Discharge Air Temperature |
90 |
Sets the minimum discharge air temperature during a heat call. Almost always set at 90°F/32°C, some older heaters may be found at 100°F/38°C and should be set to 90°F/32°C |
C011 |
L000 |
Room Temperature Setpoint (Home) |
70 |
Do not adjust this setting in this configuration menu, it is handled through the up/down arrow on the display. |
C012 |
L001 |
Room Temperature Setpoint (Away) |
60 |
If using a device such as the new Steffes Connect Transceiver to reduce the room temperature when the area is unoccupied, this is the setting used by the heater. |
C013-C021 |
L003, L062-L073 |
Time Clock Module Configuration |
C013:4, rest:0:00 |
These configuration settings are used to configure the peak control times when utilizing the optional Time Clock Module. Refer to the installation and configuration instructions included with the module for more information. |