Location 36 (L036)

Configuration 5 (C005)

Factory

Default

Default

Range

Description / Function 

0

0 to 255

2100 Series

Control Switch Configuration - Determines how the heater reacts to a control switch signaling device. In standard configuration, a "closed" control switch indicates an on-peak (control) period, an anticipated peak period, or room temperature setback period. Each of these signals can be inverted.

Value

Option Selected

0

CLOSED control switch indicates a Peak (Control) time, an Anticipated Peak time, or a Room Temperature Set Back period.

1

OPEN control switch indicates a Peak (Control) time.

2

OPEN control switch indicates an Anticipated Peak time.

4

OPEN control switch indicates a Room Temperature Set Back period.

8

Not used in 2100 Series.

16

An OPEN thermostat switch enables Y, Stage 1 heat call, when using a low voltage thermostat.

32

An OPEN thermostat switch enables W, Stage 2 heat call, when using a low voltage thermostat.

64

An OPEN thermostat switch enables E, Emergency Heat, when using a low voltage thermostat.

1

0 to 255

3100/4100/5100 SERIES

Control Switch Configuration - Determines how the system reacts to a control switch signaling device. In standard configuration, a "closed" control switch indicates an off-peak (charge) period, an anticipated peak period, a room temperature setback period or a cooling call (the "O" wiring position on compressor is energized).

Value

Option Selected

0

CLOSED control switch indicates a Peak (Control) time, an Anticipated Peak time, or a Room Temperature Set Back period.

1

OPEN control switch indicates a Peak (Control) time.

2

OPEN control switch indicates an Anticipated Peak time.

4

Not used in 3100, 4100, or 5100 Series.

8

An OPEN thermostat switch enables O, reversing valve.

16

OPEN thermostat switch enables Y, Stage 1.

32

OPEN thermostat switch enables W, Stage 2.

64

OPEN thermostat switch enables E, Emergency Heat.