Value
|
Option Selected
|
1
|
4100 Series Only - Allows the core blowers to run independently.
|
2
|
Output temperature reaction setting. Must be used in all models.
|
8
|
Enables compressor control if there is a "COOL" call during a peak (control) period.
|
16
|
Enables Comfort Override (Comfort override allows the heating elements to be energized, even during peak control periods, provided brick core is depleted and there is a Stage 2 or Stage 3 heat call.)
NOTE: Comfort Override will override the "MA" command for load management (version 2.06 or higher only)
|
32
|
Enables compressor cycling. If it is a peak (control) period and the system receives a cooling call, the compressor turns off and on in 20 minute intervals. (Off 20 minutes, on 20 minutes, off 20 minutes, etc.)
|
64
|
Version 2.10 and below: Unused
Version 2.12 and higher: Locks out the core blower when the core is empty, i.e. less than 100°F, and allows it to come on again above 150°F.
|
128
|
Interfaces the system with a heat pump that has a reversing valve which is energized for heating (i.e., Rheem, Ruud, etc.) Most heat pumps energize the reversing valve for cooling and will not require this bit.
|