Location 37 (L037)

Configuration 6 (C006)

Factory

Default

Default

Range

Description / Function

2100

6

0 to 255

2100 Series

Output Control Configuration - Configures the output controls of the system.

 

Value

Option Selected

2

Output temperature reaction setting. Must be used in all models.

4

Helps maintain room temperature set point.

64

Version 2.10 and below: Unused

Version 2.12 and higher: Locks out the core blower when the core is empty, i.e. less than 100°F, and allows it to come on again above 150°F.

3100

2

4100

3

5100

2

0 to 255

3100/4100/5100 Series

Output Control Configuration - Configures the output controls of the system.

 

Value

Option Selected

1

4100 Series Only - Allows the core blowers to run independently.

2

Output temperature reaction setting. Must be used in all models.

8

Enables compressor control if there is a "COOL" call during a peak (control) period.

16

Enables Comfort Override (Comfort override allows the heating elements to be energized, even during peak control periods, provided brick core is depleted and there is a Stage 2 or Stage 3 heat call.)

NOTE: Comfort Override will override the "MA" command for load management (version 2.06 or higher only)

32

Enables compressor cycling. If it is a peak (control) period and the system receives a cooling call, the compressor turns off and on in 20 minute intervals. (Off 20 minutes, on 20 minutes, off 20 minutes, etc.)

64

Version 2.10 and below: Unused

Version 2.12 and higher: Locks out the core blower when the core is empty, i.e. less than 100°F, and allows it to come on again above 150°F.

128

Interfaces the system with a heat pump that has a reversing valve which is energized for heating (i.e., Rheem, Ruud, etc.) Most heat pumps energize the reversing valve for cooling and will not require this bit.