Faceplate Display Information - Selects the items to display on the faceplate during the normal operating mode when pressing the up or down arrow button.
To determine the value, check the options desired from the list below. Then, add the numbers from the "Value" column and enter the sum into this location.
Value
|
Option Selected
|
1
|
Display Current Time. (Not recommended without optional time clock module.)
|
2
|
Display Day of the Week. (Not recommended without optional time clock module.)
|
4
|
Display Current Operating Mode (C, P, or A) and Current Room Temperature. (Format: Cxxx, Pxxx, or Axxx)
|
8
|
Not used. If set, the system will display ”d 0”.
|
16
|
Display Current Outdoor Temperature. (Format: Oxxx)
|
|
244
|
0 to 255
|
3100/4100/4200/5100 Series
Faceplate Display Information - Selects the items to display on the faceplate during the normal operating mode when pressing the up or down arrow button.
To determine the value, check the options desired from the list below. Then, add the numbers from the "Value" column and enter the sum into this location.
Value
|
Option Selected
|
1
|
Display Current Time. (Not recommended without optional time clock module.)
|
2
|
Display Day of the Week. (Not recommended without optional time clock module.)
|
4
|
Display Current Operating Mode (C, P, or A). If the optional freeze protection sensor is installed; current room temperature is also displayed. (Format: Cxxx, Pxxx, or Axxx)
|
8
|
Not used. If set, the system will display ”d 0”.
|
16
|
Display Current Outdoor Temperature. (Format: Oxxx)
|
32
|
Display Heat Call Status. If interfaced with an air conditioner or heat pump, cooling status is also displayed. (Format: HC_x or COOL)
|
64
|
Display Current Core Charge Level Percentage. (Format: CL:xx)
|
128
|
Display Current Target Level Percentage. (Format: tL:xx)
|
|
FACEPLATE DISPLAY CHARACTER REFERENCE – (”x” represents a digit on the faceplate.)
|
C xx
|
Charge period (off-peak) and current room temperature if a freeze protection sensor is installed.
|
P xx
|
Peak period (on-peak) and current room temperature if a freeze protection sensor is installed.
|
A xx
|
Anticipated peak period (pre-peak) and current room temperature if freeze protection sensor is installed.
|
Oxxx
|
Current outdoor temperature.
|
HC_x
|
Type of heat call (F = Fan Only, 0 = No Heat Call, 1 = Stage 1, 2 = Stage 2, 3 = Emergency Heat or Hydronic, COOL = Cooling Call).
|
CLxx
|
Current charge level - Indicates the percentage of heat currently stored in the brick core.
|
tlxx
|
Target charge level - Indicates the percentage of brick core charge the heater is targeting.
|
|