Factory Default |
Default Range |
Description / Function |
---|---|---|
60 (°F) 16 (°C) |
Determined by values in L007/L008 |
2100 Series Room Temperature Set Back - Room temperature to be maintained in response to a set back signal. This value may not be set below the value in L008 (Minimum Room Temperature Set Point). A set back signal can be initiated from a low voltage input or Steffes Power Line Carrier (PLC) system. NOTE: In applications where a Steffes Time Clock Module is being used to signal room temperature set back, the value in this location is not applicable. (Reference L035, L060, and L074-L089.) |
3100/4100 Series Specialty Applications Only |
||
140 (°F) 60 (°C) |
Determined by values in L007/L008. |
5100 Series Minimum Outlet Water Temperature - Minimum outlet water temperature to be targeted. This value cannot be set higher than the value in L007 or lower than the value in L008. The targeted outlet water temperature is also affected by the values in L012 and L013. Example: If the values of L012 = 60; L013 = 20; L000 = 180; L001 = 140, an outdoor temperature of 40°F would result in a targeted outlet water temperature of 160°F. NOTE: If an outdoor temperature sensor is NOT installed, the system targets the outlet water temperature as set in L000. |