THIS KIT MUST BE INSTALLED BY A QUALIFIED TECHNICIAN PER THE INSTRUCTIONS BELOW TO ENSURE PROPER OPERATION.
WARNING
HAZARDOUS VOLTAGE: Risk of electric shock. Can cause injury or death. System may be connected to more than one branch circuit. Disconnect power to all circuits before servicing.
Set L098
Set the value of Location 98 (L098) to the appropriate value shown in Table 3. Location 98 will revert to a value of zero (0) upon leaving the location.
Table 3 - Initial Location 98 Setup Values
Series |
Standard |
Nova Scotia |
Ontario |
---|---|---|---|
2000 Quantum |
21 |
20 |
22 |
Verify These Locations
Set/verify the values as shown in Table 4. These values correspond to the specific model of heating system and blower information.
Table 4 - 2000 Series Quantum Location Values
Model |
||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Blower Mfg |
FASCO |
Jakel or P-TECH |
||||||||||
Location |
2002 120V |
2002 |
2003 |
2004 |
2005 |
2006 |
2002 120V |
2002 |
2003 |
2004 |
2005 |
2006 |
1 |
240V = 1 208V = 5 |
1 |
240V = 1 208V = 10 |
|||||||||
20 |
20 |
65 |
110 |
155 |
200 |
20 |
20 |
65 |
110 |
155 |
200 |
|
55°F/12°C |
55°F/12°C |
|||||||||||
L052 |
12 |
12 |
||||||||||
4 |
4 |
|||||||||||
1 |
1 |
|||||||||||
220 |
240 |
|||||||||||
150 |
100 |
Configure the System
Configure the system using the Configuration Guide (Table 5) below. See here for help accessing the configuration menu.
NOTE: Only update configurations C000 – C006 as needed for the application.
Verify Operation
Verify operation and install painted front cover.