NOTE: Locations L060 through L089 are time clock related programs. The optional Steffes Time Clock Module must be installed in order to utilize the features described in these locations
Factory Default |
Default Range |
Description / Function |
---|---|---|
0:00 |
0:00 to 16:00 |
All Systems Version 2.08 and lower: Weekday Peak Time #3 Duration - Sets duration of the 3rd weekday scheduled peak period (as set in L066). Value specified in 15-minute intervals. |
P0:00 |
P0:00 to P9:45 followed by A0:00 to A9:45 |
Version 2.10 and Higher: Time #3 Duration - If L060 does not include the 16 bit: 3rd Weekday Peak or A-Peak duration: Sets duration of the 3rd weekday scheduled peak period (as set in L066). Value specified in 15-minute intervals.
If L060 includes the 16 bit: 3rd Winter Peak or A-Peak duration: Time durations preceded by "P" set the unit to peak starting at the time set in L066 for the duration as set by this location, up to 9 hours and 45 minutes. Time durations preceded by "A" set the heater to use the Anticipated Peak method of charge control (L011) and display "A" mode starting at the time set in L066. Using an annual schedule, this value applies to every day following the 1st day of the month selected in L058 until the 1st day of the month selected in L059. When setting this location, after reaching P9:45, the value steps to A0:00 and continues to A9:45
This setting applies to weekends if L060 contains the 64 bit, otherwise weekends are off-peak continuously. If reading this value through the communication port, 0 = P, 1 = A, e.g. a value of "01:00" through the communications port displays and functions as P1:00, a value of "11:00" through the communication port displays and functions as A1:00. |