Factory Default |
Default Range |
Description / Function |
||||||||
---|---|---|---|---|---|---|---|---|---|---|
100 |
0 to 100 |
All Systems Manual Charge Control Set Point - Specifies the percentage of core charge the system targets during an off-peak or anticipated peak period when using a manual charge control method (subroutine 2 or 6 in L010, L011, L030, and L032). When using charge subroutines 2 or 6, L002 should be set to allow adjustment from the faceplate (Reference the 16 bit in L002), included in factory default of 24 for 2100 series.
NOTE: If using a charge subroutine of 2 or 6, the value in L099 must NOT be set lower than a value of fifteen (15). |