NOTE: L090 through L098 are Configuration Locations. These locations are for setting up the system and access to editing them is only available in the first 4 minutes after powering up the system
Factory Default |
Default Range |
Description / Function |
---|---|---|
2100 150 (°F) 66 (°C)
3100/4100 170 (°F) 76 (°C)
4200 170 (°F) 76 (°C)
5100 125 (°F) 52 (°C) |
100 to 200 (°F)
38 to 93 (°C) |
All Systems Maximum Temperature of Control Board - Factory Purposes Only. If the temperature of the control board goes 5 degrees or more above this temperature and Error 7 ("ER07") will be displayed and on 2100 Series and Comfort Plus systems with PSC supply air blowers, the blower will energize. The blower will not energize on 3100/4100/5100 Series systems with variable speed supply air blowers. NOTE: Do not change from the default value without factory authorization. |