4200
9
|
0 to 255
|
Optional Controls Configuration - Interfaces the system with optional sensors and controls that may be used in the application. Shortcuts to some user control functions are also enabled in this location.
Value
|
Option Selected
|
1
|
Enable Hard Wired Outdoor Temperature Sensor. (Only applicable if using a charge subroutine of 3, 5, 7, 8 or 9 in L010, L011, L030, and/or L032).
|
2
|
Currently Not Used.
|
4
|
Enable the Time Clock Module Option and add both "CLOC" and "DAy" to the menu on the display. (Refer to L060-L089 for setting desired function and operation of the time clock module.)
|
8
|
Ability to Enable/Disable Charge Control Override Option from the faceplate. (This option allows user to initiate a one-time full core charge. When utilized, all charge control settings are temporarily overridden to force the heater to its maximum charge during the off-peak period.)
NOTE: This is not a Peak override.
|
16
|
Currently Not Used.
|
32
|
Currently Not Used.
|
64
|
Currently Not Used.
|
128
|
Currently Not Used.
|
|