Location 14 (L014)

Factory

Default

Default

Range

Description / Function

0

-20 to 20

2100 Series

Room Temperature Display Calibration - Used to calibrate the room temperature reading of the heater. This value is the number of degrees the heater will increase or decrease the room temperature reading by.

Example: If the heater is currently displaying a room temperature of 68°F, increasing the current value in this location by four (4) changes the displayed room temperature to 72°F.

3100/4100 Series

Currently not utilized.

5

-20 to 20

5100 Series

Water Temperature Display Calibration - Used to calibrate the water temperature reading of the system. This value is the number of degrees the outlet water temperature reading will be increased or decreased by.

Example: If the heater is currently displaying a water temperature of 120°F, increasing the current value in this location by ten (10) changes the displayed room temperature to 130°F.