Model |
4210 |
---|---|
Charging Input (kW) |
16.0 |
Single Feed: Minimum Circuit Ampacity (240V) (Includes 25% derate for continuous load) |
92 AMP |
Charging Circuits Required (240 V System - Multiple Feed) |
2 - 50 AMP |
Maximum Core and Supply Blower Load |
7 AMP |
Element Voltage | 240 V/60 Hz |
Blowers/System Controls Voltage |
240 V/60 Hz |
Storage Capacity kWh BTU |
80 272,960 |
Dimensions Including Air Handler (W x D x H in inches) |
43 x 44 x 47 |
Air Handler Duct Openings (W x D x H in inches) Supply Air Outlet Return Air Inlet |
18.6 x 18.1 16 x 16 |
Approximate Heater Weight |
333 lbs |
Approximate Brick Weight |
1,134 lbs |
Approximate Air Handler Weight |
96 lbs |
Approximate Installed Weight |
1,563 lbs |
Number of Elements |
8 |
Number of Bricks |
72 |
1/2 HP Supply Blower Air Delivery |
100 - 1300 CFM |
Optional Return Air Plenum A return air plenum can be ordered as an optional accessory with Serenity. The dimensions listed are those that the optional return air plenum can accommodate. For larger coils, the return air plenum must be installer supplied. If using an air conditioner or heat pump system, that system must include the indoor coil or the outdoor compressor system as standard equipment. Maximum Indoor Coil: Serenity can accommodate most heat pump or air conditioner indoor coils, provided the heat pump or air conditioner is sized in accordance to supply air delivery rates of the system. Capacity Front Access Dimensions (in inches) Inner Dimensions (W x D x H in inches) |
1 ½ to 3 TON 20 x 20 21 x 21 x 22
|
1206130 Rev 0 03/14/2025