Location 37 (L037)

Configuration 6 (C006)

Factory

Default

Default

Range

Description / Function

4200

2

0 to 255

4200 Series

Output Control Configuration - Configures the output controls of the system.

 

Value

Option Selected

1

Currently Not Used

2

Output temperature reaction setting. Must be used in all models.

4

Currently Not Used.

8

Enables compressor control if there is a "COOL" call during a peak (control) period.

16

Enables Comfort Override (Comfort override allows the heating elements to be energized, even during peak control periods, provided brick core is depleted and there is a Stage 2 or Stage 3 heat call.)

NOTE: Comfort Override will override the "MA" command for load management (version 2.06 or higher only)

32

Enables compressor cycling. If it is a peak (control) period and the system receives a cooling call, the compressor turns off and on in 20 minute intervals. (Off 20 minutes, on 20 minutes, off 20 minutes, etc.)

64

Currently Not Used.

128

Interfaces the system with a heat pump that has a reversing valve which is energized for heating (i.e., Rheem, Ruud, etc.) Most heat pumps energize the reversing valve for cooling and will not require this bit.