Line Voltage Connections - Transmitter

This Device can be Connected to 120V or 208V/240V, Single Phase.

NOTE: In most applications, optimum performance is achieved when connected to 208V/240V.

warning iconWARNING

HAZARDOUS VOLTAGE: Risk of electric shock, injury, or death. All line voltage wiring connections MUST be made within and routed through the line voltage raceway of the transmitter's factory installed junction box.

The PLC transmitter is factory configured for 208V/240V field connections. DO NOT connect the transmitter to 277V unless the identification label indicates it is suitable for 277V. A three-phase option is available as a special order.

If the transmitter is to be connected to 120V, transformer tapping MUST be changed. To change transformer tapping to 120V, move the black wire jumper to positions P2 and 110 in the line voltage terminal strip. Move the factory installed line voltage connections to the 110 and L1 positions in the line voltage connections terminal strip. (See Circuit Board Configuration for reference to proper placement of the jumper and wires.)