Transceiver (Non-Current XCVR1) - 5-Pole Line Voltage Connections

yellow triangle with lightning boltWARNING

Hazardous Voltage. Can cause injury or death.

  1. The transceiver can be powered with 120 VAC or 208/240 VAC. Before connecting power to the transceiver, the circuit board MUST be tapped for the appropriate input voltage as shown.

    NOTE: 208VAC/240VAC is factory default.

  1. Power to the circuit board is fed through Circuit 1. Connect the two wires labeled "Circuit 1" to a breaker in the breaker panel to power the 5-pole transceiver.

    NOTE: Any load connected to L1 and L2 on Circuit 1 of the terminal block will remain uncontrolled.

SecureGround™ Ground Bond

NOTE: This transceiver has SecureGround™ ground wire bond points. Use this procedure to connect line-voltage ground wires to the enclosure throughout this installation instruction.

  1. If used, connect ground wire to SecureGround™ screw by removing 1±1/8" (25.4±3 mm) insulation from ground wire.

    NOTE: Anchor hole accepts 14 to 10 AWG solid conductor.

  1. Insert end of wire into SecureGround™ anchor hole. Hold wire firmly and bend it clockwise, 350º around screw shank.

    NOTE: Make sure no insulation is between wire and screw head.

  1. Tighten screw securely.