DIP Switch 7 - CCRP

Negative Outdoor Temperature Calibration

This DIP switch is used to calibrate the outdoor temperature sensor information downward if it is reading higher than the actual outdoor temperature. In most situations, this procedure does not need to be performed.

Factory Default Setting = OFF

Off = Standard operating position.

On = A negative 5°F (-5°F) outdoor temperature calibration is applied.