DIP Switch 1 - CCRP

Invert Peak

This DIP switch is used to match the utility’s signaling device to the Steffes microprocessor based heating equipment and the Steffes PLC Receiver(s) for peak control purposes.

Factory Default Setting = OFF

Off = An open utility switch will signal an off-peak time to the heater (charging is enabled in the ETS heater). A closed utility switch will signal an on-peak time (charging is disabled in the ETS heater).

On = A closed utility switch will signal an off-peak time to the heater (charging is enabled in the ETS heater). An open utility switch will signal an on-peak time (charging is disabled in the ETS heater).

NOTE: The peak control signal is a priority signal. When the room heating units or mini receiver controlled devices are receiving a peak signal, an anticipated peak signal will be overridden.