Model |
5120 |
5130 |
5140 |
||||
|---|---|---|---|---|---|---|---|
|
Charging Input (kW) |
14.0 |
19.2 |
24.8 |
28.8 |
37.2 |
38.4 |
45.6 |
|
Single Feed: Minimum Circuit Ampacity (240V Systems) (Includes 25% Derate for Continuous Load) |
84 |
111 |
140 |
161 |
205 |
211 |
249 |
| Element Current Draw | 59 | 80 | 104 | 120 | 155 | 160 | 190 |
|
Element Circuits Required (amps) (240V System - Multiple Feed) System is factory configured with multiple line voltage, single phase circuit connections. If single feed to the element and blowers controls circuits is desired, an optional single feed kit is available. Phase balancing is recommended when making connections in 3-phase applications. |
1-20 |
1-30 |
1-40 |
4-40 |
4-50 |
4-50 |
4-60 |
|
Number of Elements |
8 |
12 |
16 |
||||
|
Maximum Pump and Blower/Control Load |
10 Amps |
||||||
|
Pump Voltage |
120V (Neutral Conductor Required) |
||||||
|
Blowers/Controls Voltage |
240/208V / 60 Hz |
||||||
|
Element Voltage |
240V Standard (208V optional as special factory order) / 60 Hz NOTE: The 240V Element circuits can be connected to 208V in standard configurations; however, the charging input of the system will be derated by 25%. |
||||||
|
Dimensions (W x D x H in inches) |
29.2" x 47.5" x 46" |
29.2" x 47.5" x 57" |
29.2" x 47.5" x 68" |
||||
|
Storage Capacity The size and heating ability of the system required for an installation is dependent on the heat loss of the area and the power company’s off-peak hours. In addition, if the system is not installed within the heated area, heat lost statically must be considered when sizing a system. Contact Steffes for assistance in selecting an appropriately sized system. kWh BTU |
120 409,440 |
180 614,160 |
240 818,880 |
||||
|
Pipe Size - Water Inlet/Water Outlet |
1" |
||||||
|
Outlet Water Temperature Selection Range |
50°F/10°C to 185°F/85°C |
||||||
|
Maximum Working Pressure |
Standard: 20 PSIG requires 30 PSI Pressure Relief Valve Optional: 60 PSIG requires 75 PSI Pressure Relief Valve; 125 PSIG requires 150 PSI Pressure Relief Valve |
||||||
|
Maximum Flow Rate (primary loop) |
1 GPM per 10,000 BTU of required output at 20°F temperature rise (10 GPM maximum) |
||||||
|
Approximate Heater Weight Contact a building contractor or architect if you have structural weight concerns of the installation surface selected. Adhere to all national and local electrical building code placement requirements for electrical heating appliances. |
487 lbs |
544 lbs |
612 lbs |
||||
|
Approximate Brick Weight |
1,702 lb |
2,458 lb |
3,214 lb |
||||
|
Approximate Installed Weight |
2,189 lb |
3,002 lb |
3,826 lb |
||||
|
Number of Brick Whole Brick Half Brick |
105 6 |
150 12 |
198 12 |
||||
|
Maximum Maintainable Heat Loss (BTU/hr) The size and heating ability of the system required for an installation is dependent on the heat loss of the area and the power company’s off-peak hours. In addition, if the system is not installed within the heated area, heat lost statically must be considered when sizing a system. Contact Steffes for assistance in selecting an appropriately sized system. |
|||||||
|
8 Consecutive Charge Hours |
20,414 |
27,996 |
34,175 |
41,994 |
49,212 |
55,992 |
65,615 |
|
12 Consecutive Charge Hours |
30,621 |
41,994 |
45,566 |
62,991 |
65,615 |
83,988 |
87,487 |
|
6/4/6/8 Charge Strategy |
30,621 |
41,994 |
54,242 |
62,991 |
81,363 |
83,988 |
99,735 |
|
Internal Pressure Drop (assuming 50% glycol mix, see Heat Exchanger Specifications) |
0.1 ft @ 2 GPM 0.2 ft @ 4 GPM 0.4 ft @ 6 GPM 0.7 ft @ 8 GPM 1.1 ft @ 10 GPM |
||||||
Specifications - 5100 Series EN-FR Rev 1.pdf, 1206131, 05/30/2025