THIS PROCEDURE MUST BE PERFORMED BY A QUALIFIED TECHNICIAN.
THIS PROCEDURE MUST BE PERFORMED BY A QUALIFIED TECHNICIAN.
A low voltage (24 VAC) room thermostat is required for room temperature control with Serenity. Steffes recommends using a digital thermostat. If utilizing a mechanical thermostat, a load resistor may be necessary due to the low current draw (.01 amps) on the heat call input circuit of Serenity.
Figure 23
Figure 24
* If multiple inputs are active, system will display highest Heat Call values.
** Thermostat must be programmed to energize reversing valve for cooling. If outdoor unit used requires the reversing valve be energized for heating, see Configuration Menu.
Figure 25
* If multiple inputs are active, system will display highest Heat Call values.
** Thermostat must be programmed to energize reversing valve for cooling. If outdoor unit used requires the reversing valve be energized for heating, see Configuration Menu.
4200 Owner's Manual English 1201282 Rev 5