SUPPLY AIR BLOWER SPEED |
STATIC PRESSURE (INCHES WATER COLUMN) (External static pressure should not exceed .50 inches water column for 4100 Series) |
||
---|---|---|---|
0.25 |
0.50 |
0.75 |
|
HIGH (CFM) |
2200 |
1950 |
1700 |
MEDIUM HIGH (CFM) |
--- |
--- |
--- |
MEDIUM (CFM) |
See Note |
See Note |
See Note |
MEDIUM LOW (CFM) |
--- |
--- |
--- |
*LOW |
See Note |
See Note |
See Note |
* Low Speed Maximum Pressure is .25 inches water column.
Note: For CFM ratings not listed for the 3/4 HP blower options, contact the factory.