Brick Core Sensor Replacement - 3100 Series

Item #1041625R (Sensor Core Assy 3100 Repl)

warning iconWARNING

HAZARDOUS VOLTAGE: Risk of electric shock. Can cause injury or death. System may be connected to more than one branch circuit. Disconnect power to all circuits before servicing. Equipment must be installed and serviced by a qualified technician.

NOTE: Have the customer turn off the 60 amp breakers prior to service call to ensure core is cool to safely perform the brick core sensor replacement.

De-energize Unit

De-energize the system.

Remove Covers

Remove the electrical panel cover and front painted panel. Locate the core sensor inside the electrical compartment. See Figure 2.

Inside of 3120 electrical panel

Disconnect Sensor Wires

Disconnect the sensor wires from the processor control board. See Figure 1.

Control Board Connections

Cut Silicone

Using a utility knife carefully cut the high temperature silicone sealant from between the thermocouple and the galvanized panel.

Disconnect Element Wires

Disconnect the element wires from the elements and carefully lay them to the sides.

Remove Galvanized Panel

Remove the galvanized front panel.

Lift Blankets

Starting at the bottom, carefully lift each of the insulation blankets and drape them over the top of the system.

NOTE: Use face mask, gloves, and long sleeved garments when handling insulation materials in compliance with generally accepted safety practices.

Remove Air Channel

Remove the front air channel.

Remove Elements

Remove the elements from the brick core.

Unload Bricks

Unload the bricks from the left side and center of the brick core until the sensor is completely exposed. Unloading the bricks will make it easier to remove the old sensor and install the new one.

Remove Sensor

Remove the old sensor and clean any remaining silicone off the galvanized panels.

Install Sensor

Install the new sensor. Using the silicone provided, seal between the sensor and the galvanized panel of the brick core.

Reload Bricks/Install Elements

Reload the bricks and install the elements.

Install Air Channel

Install the front air channel.

Secure Blanket Insulation

Carefully lower the insulation blankets into position, one at a time. Tuck the sides of the insulation into the edges, corners and around the exposed portions of the heating elements to ensure maximum efficiency.

Install Galvanized Panel

Re-install the galvanized front panel.

Secure Element Connections

Secure element wiring harnesses to the element terminals with screw heads up and threads pointing down. Verify good tight connections

Connect Wires

Connect the sensor wires to the processor control board as shown in Figure 1.

NOTE: These sensor wires are polarity sensitive and MUST be positioned correctly to ensure proper operation of the system.

Install Covers

Install the electrical panel cover and painted front panel.

Verify Operation

Energize the system and ensure proper operation.

Instruction 1200363 Rev 2 01/31/24